NFPA 10 Test 2024-2025 Edition. Real
Questions and Correct, Verified
Answers. Graded A+
10 lb ABC extinguishers have a 5-20 foot discharge stream and a discharge time of 2
minutes - ANSFalse
110 lbs to 315 lbs ABC wheeled fire extinguishers have a 15-45 foot discharge range
and a 30-60 second discharge time. - ANSTrue
2 1/2 gallon water extinguisher have a horizontal stream range of 30-40 feet and an
approximate discharge time of 1 minute - ANSTrue
5 lb CO2 extinguisher have a 3-8 foot horizontal stream range and a 8-30 second
discharge time. - ANSTrue
A condemned cylinder/fire extinguisher can only be destroyed by its owner or at the
owners direction. - ANSTrue
A cylinder containing fire extinguishing agent, nitrogen, compressed air, or other
compressed gasses at a service pressure of 500 psig or lower is: - ANSLow pressure
cylinder
A fire extinguisher inspection is: - ANSA monthly quick check
A fire extinguisher maintenance is: - ANSAn annual inspection.
A fire extinguisher shall be inspected every _____ after it has been placed into service -
ANS30 days
A stored pressure extinguisher stores the expellant gas in a separate container from the
extinguishing agent. - ANSFalse
A stored pressure water fire extinguisher rated 2A will protect an area of ____ in an
ordinary occupancy. - ANS3000 sq. Ft.
Acceptable means of identifying extinguisher locations may include: - ANSArrows,
lights, signs, coding on walls/columns. (All of the above)
AFFF and FFFP fire extingulshers can be protected against temperatures below 40° F
by adding an antifreeze charge. - ANSFalse
pf3
pf4
pf5
pf8
pf9
pfa

Partial preview of the text

Download NFPA 10 Test 2024-2025 Edition. Real Questions and Correct, Verified Answers. Graded A+ and more Exams Safety and Fire Engineering in PDF only on Docsity!

NFPA 10 Test 2024-2025 Edition. Real

Questions and Correct, Verified

Answers. Graded A+

10 lb ABC extinguishers have a 5-20 foot discharge stream and a discharge time of 2 minutes - ANSFalse 110 lbs to 315 lbs ABC wheeled fire extinguishers have a 15-45 foot discharge range and a 30-60 second discharge time. - ANSTrue 2 1/2 gallon water extinguisher have a horizontal stream range of 30-40 feet and an approximate discharge time of 1 minute - ANSTrue 5 lb CO2 extinguisher have a 3-8 foot horizontal stream range and a 8-30 second discharge time. - ANSTrue A condemned cylinder/fire extinguisher can only be destroyed by its owner or at the owners direction. - ANSTrue A cylinder containing fire extinguishing agent, nitrogen, compressed air, or other compressed gasses at a service pressure of 500 psig or lower is: - ANSLow pressure cylinder A fire extinguisher inspection is: - ANSA monthly quick check A fire extinguisher maintenance is: - ANSAn annual inspection. A fire extinguisher shall be inspected every _____ after it has been placed into service - ANS30 days A stored pressure extinguisher stores the expellant gas in a separate container from the extinguishing agent. - ANSFalse A stored pressure water fire extinguisher rated 2A will protect an area of ____ in an ordinary occupancy. - ANS3000 sq. Ft. Acceptable means of identifying extinguisher locations may include: - ANSArrows, lights, signs, coding on walls/columns. (All of the above) AFFF and FFFP fire extingulshers can be protected against temperatures below 40° F by adding an antifreeze charge. - ANSFalse

After hydrostatic testing, all extinguishers (except water types) shall have all traces of water removed - ANSTrue Agent in solid charge AFFF shall be replaced every year - ANSFalse Agent in solid charge AFFF shall be replaced every year. - ANSFalse Alkalimetal salt, used as an antifreeze medium, is used in what kind of fire extinguisher agent. - ANSLoaded stream All dry chemical and dry powder types of fire extinguishers must have what? - ANSAll traces of powder removed before filling with water. All extinguisher hose assemblies equipped with a shutoff nozzle shall be hydrostatically tested - ANSTrue All other extinguisher types may be installed where temperatures range between -30° to 125° - ANSTrue All wheeled fire extinguishers equipped with a shut off nozzle at the end of the hose must have: - ANSA special adapter to test and recharge. Aluminum shell/cylinder extinguisher must be removed from service and hydrostatic tested if exposed to temperatures exceeding 350° - ANSTrue An inspection of a fire extinguisher is a quick check and is required to be done at least monthly. - ANSTrue At the time of annual maintenance the tamper seal on the rechargeable fire extinguisher shall be removed by operating pull pin or locking device. - ANSTrue Bromochlorodiflouromethane is Halon 1301. - ANSFalse Burning metals - ANSKnown as class D fires and may react violently to water and significantly increase hazards associated with burning metals. Calcium Chloride solutions shall not be used in stainless steel extinguishers - ANSTrue Can you use loaded stream on Class B fires? - ANSNo Carbon Dioxide extinguishers having a specification of ICC3 shall be tested at 3000 psi.

  • ANSTrue Carbon dioxide fire extinguishers shall be tested at 5/3 the service pressure as stamped into the cylinder. - ANSTrue

Define Class D Fire - ANSCombustible Metals Define recharging - ANSRefill extinguisher with proper agent. Dry chemical hose assemblies requiring hydrostatic test shall be tested to 300 psi or at extinguisher service pressure, whichever is greater. - ANSTrue Dry chemical is designed for Class A and Class B fires and is also a non conductor of electricity and may be used on energized electrical equipment. - ANSTrue. During hydrostatic testing all fire extinguishers and hose assemblies that require hydrostatic testing must be placed in a protective cage. - ANSTrue Each floor level must be looked at as a separate hazard. - ANSTrue Factory Test Pressure is the pressure at which the shell was tested at the time of the manufacture and is shown on the extinguisher nameplate. - ANSTrue Fire extinguishers for protecting Class A hazards shall be selected from the following types. - ANSWater, multipurpose dry chemicals, halogenated types, all of the above. Fire extinguishers for protecting class C hazards shall be selected from the following types - ANSCO2 and dry chemical Fire extinguishers removed for 6-year maintenance or hydrostatic testing shall be emptied. - ANSTrue Fire extinguishers shall be installed in such a way that the fire extinguisher operating instructions facing outward - ANSTrue Fire extinguishers shall be located along normal paths of travel, including exits from areas. - ANSTrue Fire extinguishers suitable for more than one class of fire should be identified by multiple symbols placed in a vertical sequence. - ANSFalse Fire extinguishers weighing less than 40lbs shall be installed so that the top of the extinguishers is not more than 6 feet from the floor. - ANSFalse Fire extinguishers weighing more than 40lbs shall be installed so that the top of the extinguisher is no more than 3.5 feet from the floor. - ANSTrue First 4 principles of selecting fire extinguishers: - ANSEase of use, physical ability of people, effectiveness of extinguisher, hazards in area.

For an extra hazard Class B fire and 80b rate fire extinguisher the maximum travel distance to the extinguisher is - ANS50 feet For payment of the fee, checks are made payable to: - ANSTreasurer- state of Ohio For the purposes in NFPA 10, High pressure cylinders are those containing nitrogen, compressed air, CO2, or other gases at pressures higher than 500psig - ANSTrue Halon Extinguisher Recharge- if the extinguisher valve is removed for service, what is the recommended? - ANSPurge extinguisher with nitrogen High pressure cylinders and cartridges including nitrogen cylinders and cartridges used as an expellant for wheeled fire extinguisher shall not be hydrostatically tested every 5 years. - ANSFalse How much is the individual certification fee - ANS50$ How much is the individual renewal application fee? - ANS40$ How often must the following fire extinguishers be hydrostatic tested? (Years) - ANSCarbon Dioxide (5), Dry Chemical (12) Water Type (5), Halon 1211 (12), Cartridge type dry chemicals (2). Hydrotest labels should be printed in black with a light blue background - ANSFalse If a building is properly protected by uniformly spaced 1 1/2 inch fire hose station, for use by the occupants up to 1/4 of the compliment of fire extinguishers can be omitted from building protection. - ANSFalse If heat is used to remove water from a cylinder/fire extinguisher, the temperature within the shell must not exceed - ANS150° In NFPA "shall" is used as a recommendation and is not a requirement. - ANSFalse In NFPA "should" indicates a mandatory requirement. - ANS In no case shall the clearance between the bottom of the extinguisher and the floor be less than 4 inches. - ANSFalse In what year did the amendments to the protocol call for a worldwide cessation of production of Halon 1211? - ANS Industrial Grade nitrogen with a few point of -60° or lower shall be sued to pressurize stored pressure dry chemical and Halon fire extinguishers. - ANSTrue

Rechargeable extinguishers are marked recharged immediately after any use. - ANSTrue Replacement pressure gauges shall be checked for: - ANSProper service pressure, compatibility with extinguisher agent, compatibility with extinguisher valve material. (All of the above) Required building protection shall not be provided by the fire extinguishers for Class A fires. - ANSFalse Requirements of NFPA 10 are - ANSMinimum Service pressure is the pressure that is indicated on the gauge and nameplate of a fire extinguisher. - ANSTrue Servicing includes one or more of the following: (1) maintenance (2) recharging (3) hydrostatic testing. - ANSTrue Some fire extinguishers marked non refillable may be recharged by competent fire equipment dealers. - ANSFalse Stored pressure and self-expelling fire extinguishers shall be _______ after recharging.

  • ANSLeak tested Stored pressure extinguishers shall be tested at the factory test pressure not to exceed 3 times the service pressure. - ANSTrue Stored pressure extinguishers that require 12-year hydrostatic testing shall be torn down and internally examined every: - ANS6 years The actual walking distance from any point to the nearest fire extinguishers fulfilling hazard requirement is: - ANSNone of the above. The amount of recharge agent shall be verified by: - ANSWeighing The capacity of the fire extinguisher supplied for each major Class C hazard situation must be individually judged according to: - ANSSize of electrical equipment, configuration of equipment, effective range of FE amount of class A and B material. The classification and rating system as used in the NFPA 10 is that of: - ANSUnderwriters Laboratories The classification of fire extinguishers shall consist of a _______ that indicates the class of fire on which an extinguisher has been found to be effective, preceded by a rating

______ (Class A and B only) that indicates the relative extinguishing effectiveness. - ANSLetter, Number The intended position for operating instructions is usually located: - ANSOn the front of the extinguisher The interstate commerce commission had jurisdiction over high-pressure cylinders and cartridges prior to 1967. - ANSTrue The material protocol was signed on: - ANSSeptember 16, 1987 The principle advantage of CO2 fire extinguisher is: - ANSLeaves no residue The provisions of NFPA 10 apply to the selection, installation, inspection, maintenance, and testing of portable extinguishing equipment. - ANSTrue The term approved means acceptable to the authority having jurisdiction. - ANSTrue The use of a Carbon Dioxide fire extinguisher - ANSShould not be used in confined spaces This is a hard test - ANSTrue To protect a flammable liquid hazard of appreciable depth that is 6' x 10' you would need a _____ rated fire extinguisher - ANS120B Two or more lesser rated B fire extinguishers shall not be combined to meet the basic minimum rating requirements. - ANSTrue Water extinguisher may only be installed where temperatures range between 40° and 120° - ANSTrue Water extinguisher may only be installed where temperatures range between 40°-120° - ANSTrue What Chemical is in a Multipurpose Dry Chemical Extinguisher? - ANSAmmonium Phosphate. What chemical may be used in a Dry Chemical extinguisher primarily intended for use on Class B and Class C fires? - ANSSodium Bicarbonate, Potassium Bicarbonate, Potassium Bicarbonate Urea Base, Potassium Chloride Base, Bicarbonate Urea Base. (All of the above) What class is a water extinguisher? - ANSClass A

What type of fire involves Class B materials in motion, such as pouring, running, or dripping, flammable liquids. Generally includes vertical as well as one or more horizontal surfaces - ANS3 dimensional class B fires When can a Class A or Class B rated fire extinguisher be used safely on Class C Fires?

  • ANSDeenergize equipment When hydrostatic testing low pressure cylinders, pressure is applied at a rate so that pressure is not reached in less than 30 seconds and pressure must be maintained for at least 30 seconds. - ANSTrue When the applicable maintenance procedures are performed during periodic recharging or hydrostatic testing the 6 year requirement shall begin from that date. - ANSTrue When the electrical power is disconnected from an energized electrical fire, the fire changes character to that of a Class A or Class B or a combination if both Class A and B. - ANSTrue Where Is T.C.s jurisdiction - ANSCanada Where markings are applied to walls to identify extinguisher locations, they should permit easy legibility at a distance of 15 feet. - ANSTrue Which of the following conditions may result in the condemning of a fire extinguisher during inspection. - ANSAll of the above.